Governor Droop Control
GOVERNOR DROOP CONTROL
Mobin Ahmed ETO
HOD – Electrical, BP Marine Academy
Governor Speed Droop - Speed Droop is a speed control mode of a
governor of prime mover driving an alternator connected to bus. This is also
known as Governor Droop. Speed droop is a governor function which reduces the
governor reference speed as fuel position (load) increases. All engine controls
use the principle of droop to provide stable operation.
Governor droop
allows the engine to run at lower speed when the load increases and at rated
speed at no load.
Droop is expressed as a percentage of the original
frequency (speed) setting from no load to full load.
% DROOP = (fNL – fFL)
*100/fFL %
Where,
fNL is No load frequency
fFL is Full Load frequency
Normal recommended percent of droop is 3 to 5 % of
the reference frequency (speed) over the full range of the governor output.
Thus a 4% governor droop is having a frequency of 62.4 Hz at no load will be
reduce to 60 Hz at full load. Droop causes the governor speed reference or
frequency to decrease as load increases. This allows the governor to vary the
load since the frequency (speed) cannot change and remain constant (as shown in
below fig. 1). This mode allows alternators to run in parallel, so that loads
are shared among generators in proportion to their power rating.
In the below fig. 2 Alternator has a% droop. The
Governor droop and fNL can be found out by similar triangle proportions and
slope equation of straight-line y = mx + b.
Governor Droop (GD) = (fNL – fFL)/ PFL = ![]()
Also, GD = GSR*fFL/PFL
Where GSR is Governor Speed
Regulation or Droop%
PFL
is full load power at full load frequency (fFL)
Marine Alternators are of same make & model. So,
their power ratings are always similar. Their Governor droop settings are
always kept exactly same. Hence, by increasing and decreasing the governor
speed reference setting (No Load frequency), active loads are shared among them
proportionally to their governor speed reference setting. Alternator which is
having more governor speed reference setting will share more load and less
governor speed reference setting will share less load.
Active Power division between two Identical
Alternators having same Governor Droop setting - We know that Speed is proportional to frequency (Ns
. If speed increases frequency also increases and
vice-versa. When two alternators running in parallel, the loads on an engine
are determined by the reference speed setting of the droop governor. In fig. 3,
the graph shows that the amount of loads are shared by alternators are where
the droop line intersects (point M) the common frequency (PQ line) of both alternators.
If the location of this line is moved (New intersects point R), either by
changing the reference speed or the amount of droop (is seldom changed) in the
unit, the amount of load shared will also be changed.
Increasing the reference speed setting of one
governor cannot cause a change in the frequency (speed) of the Alternator, but
it will cause a change in the amount of load the engine is carrying.
The load transfer is accomplished by adjusting their
governor’s no-load settings with same droop slope. If load is increased in
Alternator B, speed will decrease, hence the frequency will decrease. In same
time load is decreased in Alternator A, so, the speed will increase, hence the
frequency will increase. Now, the frequency constant (say 60 Hz) to be kept
constant. To achieved this, Alternator B raises its governor characteristics by
raising no-load frequency. And Alternator A lowers its governor characteristics
by lowering no-load frequency (both characteristics shown by dotted lines in
fig. 3)
Active Power division between two Identical
Alternators having different Governor Droop setting - When two identical
alternators operating in parallel having different droop characteristics, the active
load proportion shared by each alternator will depend on the total load and the
droop characteristics of each alternator. If both governor No load frequency is
same, then flatter droop will assume more load than more droop governor as
shown in fig. 4.
Notice that the amount of droop set in the governor
has little effect on the ability of the governor reference speed setting to
determine the amount of load the engine will carry. The greater the droop the
less sensitive engine load will be to speed setting. However, excessive droop
presents the possibility of overspeed should the engine be removed from the
bus, thus becoming unloaded.
Identical engines can show different characteristics,
if droop settings are not similar as shown in Fig. 4. An engine with more droop
will require a greater change in the speed setting to accomplish a given change
in load than will an engine with less droop in the governor.
If two Alternators’ governor
characteristics as shown in Fig 5, are connected in parallel on the same bus,
they must have the same frequency of operation, hence the operating point (PQ
Line shown common frequency). we can see that Alternator A delivers twice the
power of Alternator B. In order to change the power in a Alternator
for a given frequency of operation (PQ Line), one has to change the prime mover
(change the value of the no-load frequency, or Governor Reference Speed).
Changing the governor will cause the characteristic to move up and down with
the same slope in order to change the power.
Active Power division between One Isochronous
Alternator and One Alternator with Governor Droop setting
Isochronous governors - This type of governor can maintain constant speed
for any level of output power. It is also known as 0% droop mode governor.
For isochronous governors ![]()
The isochronous mode can also be used on one engine, running in parallel
with any other engine. However, unless the governors have isochronous load
sharing capabilities, no more than one of the engines running in parallel can
be in the isochronous mode.
·
Load sharing is changed by changing Alternator B’s characteristic.
·
Changing Alternator A’s characteristic, changes system frequency.
· Isochronous machine takes load variation,
while maintaining constant frequency (speed).
All engines in the system are operated in the droop mode except for one
which is operated in the isochronous mode. In this mode, the droop machines
will run at the frequency (speed) of the isochronous unit. The droop percentage
and speed settings of each droop unit are adjusted so that, it generates a set
amount of power. The output power of the Isochronous machine will change to
follow variations in the load demand while maintaining constant frequency
(speed) of the system. Maximum load for this type of system is limited to the
combined output of the Isochronous machine and the total set power output of
the droop machines. A load above this maximum will result in a decrease in
frequency (speed). The minimum system load cannot be allowed to decrease below
the combined output set for the droop machines. If it does, the system
frequency will increase and the isochronous machine can be motorized.
Formula of Active Power Division of
two Parallel Alternators
Ref:
Woodward Reference Manual, Wikipedia, MAN -Woodward Basic electronic speed
governors, Frequency Control: Speed droop & AGC by TAMU









Comments
Post a Comment